Maximum demand charges: why one half-hour sets your month

Your demand charge is set by the single highest averaging window in the month. Here is how maximum demand is measured, how the charge is worked out, and how to keep it under contract demand.

Maximum demand charges are the part of an HT bill set by the single highest demand your plant recorded in the month, measured in kVA over a short averaging window. One bad block, such as two large motors starting together, can set the demand charge for the whole month, and crossing your contract demand usually costs extra on top.

What maximum demand means

Your meter does not bill demand from an instant spike. It averages your load over a fixed window, called the demand integration period, and records the highest average in the month. The window is set by your DISCOM; 15 and 30 minutes are both common. That highest average is your recorded maximum demand (MD), shown on the bill in kVA.

Because MD is measured in kVA, not kW, power factor matters too. The same kW drawn at a lower power factor shows up as a higher kVA demand.

How the demand charge is worked out

Most HT tariffs bill demand at a fixed rupee rate per kVA per month. The billing demand is usually the higher of two numbers: your recorded MD, or a set percentage of your contract demand. That percentage, often called the minimum billing demand, is in your tariff order. So a plant that rarely runs near its contract demand still pays for a floor.

If recorded MD goes above contract demand, most tariff orders charge the excess at a higher rate, and repeated excess can lead the DISCOM to ask you to raise your contract demand. The excess-demand clause in your tariff order gives the exact rate.

Illustrative example: take the example HT bill on our home page, with a contract demand of 450 kVA, a recorded MD of 510 kVA and a demand rate of ₹300 per kVA. The demand charge is 510 × ₹300 = ₹1,53,000, and the 60 kVA above contract adds an excess-demand charge of ₹18,000 on top. These figures are an example; your rates will differ.

What usually causes a demand peak

In most plants the peak is not caused by the plant being busier than usual. It comes from loads that happen to start in the same window.

Typical causes are two furnaces or large motors started within minutes of each other at shift change; compressors all loading together after a pressure drop; chillers and process loads restarting together after a power cut; and a capacitor stage out of service, which lowers power factor and raises kVA for the same kW.

How to keep maximum demand under contract

Stagger large starts. A written start sequence at shift change, with a few minutes between big motors, often does more than any equipment.

Watch the running window, not the last one. By the time the bill arrives, the month is already set. What helps is a warning while the current window is still open, so the shift in-charge can hold a load for a few minutes.

Keep power factor up. Check capacitor banks and APFC panels regularly; a failed stage raises kVA quietly.

Review contract demand once a year. If recorded MD is well below contract every month, you may be paying for a floor you do not use. If you cross it often, raising it may cost less than the excess charges. Your DISCOM's rules on changing contract demand apply.

Ardra EMS forecasts demand for the running block and warns the shift in-charge on WhatsApp before it crosses contract demand. An energy audit compares your contract demand with your real demand, month by month.

Frequently asked questions

Is maximum demand the same as connected load?

No. Connected load is the total rating of everything installed. Maximum demand is the highest average load actually recorded in a window. Most plants never run everything at once, so MD is usually well below connected load.

Does a short motor-start spike set my MD?

Usually not on its own, because MD is an average over the integration window. A brief spike adds a little to that window's average; a large load that keeps running for most of the window adds a lot.

Can I reduce my contract demand?

Most DISCOMs allow it on application, subject to conditions such as a minimum period between changes. The process is set out in your state's supply code and tariff order.