Resources

Guide · 6 November 2026 · 4 min read

Power factor penalty: why it happens and how to stop paying it

Low power factor costs Indian plants money twice: as a penalty or extra kVAh units, and as higher kVA demand. Here is why it happens and how to stop paying for it.

A power factor penalty is an extra charge your DISCOM adds when your plant's average power factor falls below the level set in the tariff order. Under kVAh billing there may be no separate penalty line at all, but a low power factor still raises your bill, because you are billed on kVAh instead of kWh.

What power factor is

Power factor (PF) is the ratio of real power, which does useful work, to apparent power, which the supply has to carry. Real power is measured in kW and apparent power in kVA. Motors, transformers and other inductive loads also draw reactive power, which pushes PF below 1.

A PF of 0.88 means that for every 100 kVA drawn, 88 kW does work. The DISCOM's network still has to carry the full 100 kVA, which is why it charges for low PF.

Two ways low PF reaches your bill

kWh billing with a PF clause. Energy is charged on kWh and the tariff order sets a PF threshold. Below it, a penalty is added, usually as a percentage of the energy charge for each step below the threshold. Some tariffs also pay an incentive for PF above a higher level.

kVAh billing. Several states now bill HT consumers on kVAh. kVAh is roughly kWh divided by PF, so the lower your PF, the more units you are billed for the same work. There may be no line called penalty, but the cost is there.

Either way, low PF also raises your kVA demand, so it can push up the demand charge as well. Your tariff order sets the exact thresholds, steps and rates.

Illustrative example: under kVAh billing, a plant using 76,000 kWh in a month at an average PF of 0.88 is billed for about 86,400 kVAh. At a PF of 0.98 it would be billed for about 77,600 kVAh. That is close to 8,800 extra units a month for the same production, or about ₹65,000 at ₹7.40 per unit. These figures are illustrative; your rates will differ.

Common causes of low power factor

A failed capacitor stage. APFC panels switch capacitor stages in and out to match the load. When a stage fails, a fuse blows or a contactor sticks, PF drops, often without anyone noticing until the bill arrives.

Ageing capacitors. Capacitors lose capacity over time, faster in hot panels, so a bank sized correctly years ago may no longer be enough.

Lightly loaded motors and transformers. They draw reactive power out of proportion to the work they do, so idle running hurts PF as well as energy.

Harmonics. Drives and other non-linear loads can overheat capacitors and upset PF. A harmonic study should come before adding more capacitance.

How to fix it and keep it fixed

Check the APFC panel and each capacitor stage on a schedule, and replace failed stages promptly. Size correction for the real load profile, including nights and Sundays, when over-correction can happen. And watch PF per feeder, not only at the incomer, so you can see which part of the plant is pulling it down.

Ardra EMS tracks PF per feeder and flags the day a capacitor stage drops out, rather than at the end of the month. An energy audit checks a year of bills for PF penalties or kVAh effects and their likely cause.

Frequently asked questions

What power factor should a plant aim for?

Above the threshold in your tariff order, with some margin. Many plants aim for 0.95 or higher, but the number that matters is the one your DISCOM bills against.

Can power factor be too high?

A leading PF from over-correction can also be penalised under some tariffs and can raise voltage. Correction should follow the load, which is what an APFC panel is for.

Does rooftop solar change my power factor?

It can. Solar supplies real power, so the grid supplies fewer kW but much the same reactive power, which lowers the PF your DISCOM meter sees. Check PF after any solar installation.

To see whether you are paying for low PF, upload a bill to the instant AI bill check on the home page, or request a demo and go through it with an engineer.

Keep reading

Want this read on your own bill?

Request a demo
Request a demo